§ 75.1905-1 Sistem perpipaan untuk bahan bakar diesel (solar).
(a)
Sistem perpipaan bahan bakar diesel pada permukaan tanah harus dirancang dan dioperasikan sebagai sistem kering, kecuali tersedia shutdown otomatis untuk mencegah kerugian kecelakaan atau tumpahan bahan bakar yang dapat menyalakan sistem alarm.
(c)
Pipelines must have manual shutoff valves installed at the surface filling point, and at the underground discharge point.
(d)
If diesel fuel lines are not buried
in the ground sufficiently to protect them from damage, shutoff valves
must be located every 300 feet.
(f)
An automatic means must be provided
to prevent unintentional transfer of diesel fuel from the surface into
the permanent underground diesel fuel storage facility.
(g)
Diesel fuel piping systems from the
surface shall only be used to transport diesel fuel directly to
stationary tanks or diesel fuel transportation units in a permanent
underground diesel fuel storage facility.
(i)
Diesel fuel piping systems located in
entries must not be located on the same side of the entry as electric
cables or power lines. Where it is necessary for piping systems to cross
electric cables or power lines, guarding must be provided to prevent
severed electrical cables or power lines near broken fuel lines.