§ 75.1905-1 Sistem perpipaan untuk bahan bakar diesel (solar).
            
            (a)
             Sistem perpipaan bahan bakar diesel pada permukaan tanah harus dirancang dan dioperasikan sebagai sistem kering, kecuali tersedia shutdown otomatis untuk mencegah kerugian kecelakaan atau tumpahan bahan bakar yang dapat menyalakan sistem alarm. 
            
            (c)
             Pipelines must have manual shutoff valves installed at the surface filling point, and at the underground discharge point.
            
            (d)
             If diesel fuel lines are not buried 
in the ground sufficiently to protect them from damage, shutoff valves 
must be located every 300 feet.
            
            (f)
             An automatic means must be provided 
to prevent unintentional transfer of diesel fuel from the surface into 
the permanent underground diesel fuel storage facility.
            
            (g)
             Diesel fuel piping systems from the 
surface shall only be used to transport diesel fuel directly to 
stationary tanks or diesel fuel transportation units in a permanent 
underground diesel fuel storage facility.
            
            (i)
             Diesel fuel piping systems located in
 entries must not be located on the same side of the entry as electric 
cables or power lines. Where it is necessary for piping systems to cross
 electric cables or power lines, guarding must be provided to prevent 
severed electrical cables or power lines near broken fuel lines.
 